Column trees move the most critical welds in a special moment frame (SMF) or intermediate moment frame (IMF) off the iron at elevation and into the shop. That is the whole point: groove welds in a moment connection made flat or horizontal in a controlled environment, with preheat monitored by a CWI rather than on a cold column in a stiff breeze thirty feet up. The tradeoff is complexity—shop WPS documentation for column tree welds must satisfy AWS D1.1, AWS D1.8, and AISC 358 at once, and the interplay between those three documents trips up fabricators who treat the WPS as a D1.1-only exercise.
What a Column Tree Assembly Contains
A column tree typically includes a length of wide-flange column with beam stubs shop-welded to both flanges at each floor level. Each beam stub ends at a splice location clear of the connection panel zone—often at a point one-quarter to one-third of the span from the column face, depending on the moment frame connection type per AISC 358. The shop welds in the assembly include:
- Beam stub-to-column flange CJP groove welds — the demand-critical (D-C) welds that absorb seismic energy during a design earthquake
- Continuity plate CJP or complete-joint-penetration fillet groove welds — transverse stiffeners aligned with the beam flanges to distribute force through the column panel zone
- Doubler plate fillet welds — if the panel zone requires shear reinforcement per AISC 360 Equation J10-9 or the connection design
Each weld type has different WPS requirements, and they must all appear on the same WPS submittal package for the EOR's review before fabrication starts.
WPS Qualification Requirements for Demand-Critical Welds
The WPS for the beam stub-to-column flange CJP groove welds must be qualified under AWS D1.8 as well as AWS D1.1. AWS D1.8 imposes supplementary essential variables beyond those in D1.1 Table 6.6. When CVN impact testing requirements are invoked—which they always are for D-C welds in SDC D, E, or F buildings—the variables in AWS D1.1 Table 6.8 become essential. A change in any of those variables requires requalification with a new PQR that includes Charpy V-notch testing of the weld metal and heat-affected zone.
The specific variables that catch shops off guard include:
Heat input limits. AISC 358 connection prequalification conditions and AWS D1.8 place upper limits on heat input (kJ/in) for DC welds. If your production procedure runs at a higher travel speed or wire feed rate than what the PQR captured, the heat input may change enough to trigger requalification. Document the heat input range on the WPS explicitly—calculate it from the arc energy formula (amperage × voltage × 60 ÷ travel speed in in/min) and show the minimum and maximum values your process envelope produces.
Filler metal hydrogen designation. AWS D1.8 requires a minimum hydrogen designator (typically H8 or lower) for D-C weld filler metals. If your stock FCAW-G wire is designated H16, it doesn't qualify regardless of the wire's AWS A5.20 or A5.36 classification. Verify the specific wire lot's certified diffusible hydrogen level before writing it into the WPS. See diffusible hydrogen filler metal requirements under AWS D1.1 for background on the designator system.
Preheat and interpass temperature. AISC 358 connection prequalification sections specify minimum preheat temperatures that may exceed the AWS D1.1 Table 5.11 minimums for the same steel group. The WPS must state the AISC 358 or D1.8 minimum, not the lower D1.1-only value.
Continuity Plate Weld WPS
Continuity plate groove welds—where they are CJP rather than PJP per the connection design—often require a separate WPS because the joint geometry differs from the beam stub flange weld. The access conditions are different: the weld is made inside the column flanges, and the K-zone of the wide-flange column may limit weld torch angle and position.
For A992 wide-flange columns, the weld access hole geometry must conform to AISC 358 requirements for the specific connection type. Undersized or non-standard access holes change the joint root opening and can push the detail outside the prequalified joint configuration, requiring PQR qualification. Document the access hole dimensions on the WPS or the accompanying joint design detail—the EOR cannot verify compliance from the AWS D1.1 Annex J Form J-1 WPS form alone.
If continuity plate welds are classified as demand-critical (the engineer of record should state this on the structural drawings), the same CVN and hydrogen designation requirements apply. If they are non-DC, standard D1.1 Table 6.6 essential variables govern and the full D1.8 layer is not required.