Concrete-filled HSS (CFT) tube columns have become a common choice in mid- and high-rise structural frames, industrial equipment supports, and seismically demanding applications. The concrete fill dramatically increases axial and shear capacity with no increase in column footprint. However, the fill creates real constraints for the structural welder, the CWI, and the engineer selecting connection details.
A WPS written for a standard unfilled HSS column will cover the steel welding process parameters — but it will not automatically address the access, NDT, joint geometry, and thermal considerations that differ when that tube is filled with concrete. This article covers the practical WPS considerations for beam-to-column connections on CFT columns under AWS D1.1.
Rule library based on AWS D1.1:2025; verify against your governing edition — the AHJ or contract may specify 2020 or earlier.
How CFT Changes the Welding Environment
For an unfilled HSS tube column, the common welding considerations are:
- Access to the tube face for the beam-to-column connection
- Position of the weld (commonly 1G for shop-welded connections, variable for field)
- Tube wall thickness and its implications for minimum preheat
- CJP vs. PJP groove weld selection based on load demand
When the tube is concrete-filled, additional factors enter the picture:
Heat sink effect. Concrete has significant thermal mass but relatively low thermal conductivity compared to steel. This slows heat dissipation from the weld into the tube, which can slightly elevate the interpass temperature near the fill but does not change the minimum preheat requirement for the steel. The preheat minimum from Table 5.11 of AWS D1.1:2025 applies to the base metal and is not reduced because of the fill.
No access holes possible. For an unfilled tube column, the structural engineer may allow a weld access hole to relieve stress concentration or improve root pass access at a moment connection. With concrete fill, drilling or cutting an access hole in the tube wall would require extensive concrete remediation and is essentially never done. Connection details must work without access holes.
Interior back-weld is not possible. On unfilled HSS tube, it is sometimes possible to access the interior for a back-weld on a groove joint. Concrete fill eliminates that option entirely. All CJP groove welds on CFT column faces must be designed to achieve full penetration from the exterior face only, using either steel backing or a groove joint geometry that allows single-side root access.
UT is the only practical volumetric NDE option. Radiographic testing requires clear X-ray or gamma-ray transmission through the joint cross-section. Concrete fill scatters radiation in a way that makes RT film uninterpretable for the tube wall and groove weld region. Phased array UT (PAUT) or conventional UT is the NDT method of choice. The CWI should confirm UT accessibility before the connection is detailed — some HSS face geometries limit probe placement.
Connection Types and WPS Implications
Shear Tab (Single Plate) Connection
The standard shear tab welded to the face of a CFT column is a fillet weld of the plate to the tube face. This is a common, straightforward connection that does not change with the presence of concrete fill. The WPS for a fillet weld of a plate to an HSS tube face remains valid for CFT columns.
Minimum fillet weld size is determined by the thinner connected part per Table 7.7 of AWS D1.1:2025. The tube wall thickness governs when it is thinner than the plate. The filler metal, process, and essential variables in the WPS apply without modification for the fill condition.
Through-Plate Connection
Through-plate connections are common in CFT columns where high moment or combined load demands require load transfer through the column section. A flat plate is passed completely through the HSS tube — through slots cut in both tube walls — and groove-welded to the tube face on each side. The concrete is poured after the steel connection is complete.
For the WPS perspective:
- The groove weld of the through-plate to the tube face follows standard AWS D1.1 groove weld requirements. The joint must be designed to allow CJP groove weld access from the exposed exterior face, using steel backing or a suitable groove detail.
- If the slot cut into the tube wall is tight to the plate, the resulting fit-up must be within AWS D1.1 groove root opening tolerances.
- Steel backing bars placed at the bottom of the groove (on the interior tube face side) are not removable after concrete is placed. The engineer of record must accept permanent backing for this condition.
- The CWI must verify that the slot cut does not introduce notch conditions at the tube corner that would create stress concentration in the final connection.
Cap Plate and Base Plate Connections
Cap plates (top of column) and base plates (bottom of column) are fillet- or groove-welded to the tube end face. These connections are typically made before concrete is placed and are not affected by the fill condition in terms of WPS requirements.
For base plates on CFT columns, preheat requirements follow the standard A500 Grade C HSS requirements in Table 5.11 of AWS D1.1:2025, based on the tube wall thickness. After concrete is placed, the base plate weld is complete and the connection is not revisited.
Field Moment Connection — Welded Flange Plates
In some high-rise applications, beam flanges are welded directly to the CFT tube face with a CJP groove weld for moment transfer. This is the most demanding connection in terms of WPS, NDT, and inspection requirements:
- The groove weld must achieve CJP from the exposed exterior face only. This typically uses a steel backing bar tack-welded to the tube face behind the groove.
- The root pass is a critical hold point. The CWI must visually verify the root pass before proceeding, as back-gouging from the interior face is not possible.
- UT must be performed after welding is complete. The CWI should confirm with the NDT technician that probe access is sufficient on the tube face geometry — round tube faces may require curved probe shoes or PAUT scanning to achieve adequate coverage.
- For seismically detailed moment connections under AWS D1.8, the demand-critical filler metal requirements apply. The electrode must meet notch toughness requirements in addition to strength.