Lattice steel transmission towers, telecom structures, and steel poles are critical infrastructure — and their structural welds are subject to the same AWS D1.1 requirements that govern any other structural steel fabrication. Whether the tower is shop-assembled and transported to site or field-welded section by section, the fabricator and erector need documented WPS, qualified welders, and a CWI inspection program.
This article covers the WPS and inspection requirements for welding lattice steel transmission towers, telecom lattice structures, and steel monopoles under AWS D1.1:2025 — including base metal selection, joint types, preheat, field welding positions, and what the CWI needs to verify.
Code Jurisdiction for Tower Welding
AWS D1.1:2025 is the governing welding standard when the project specifications reference it. Utilities, tower manufacturers, and EPC contractors routinely cite AWS D1.1 as the baseline welding code for lattice steel transmission structures.
Some utility owners maintain supplemental welding specifications that add requirements on top of AWS D1.1 — specific filler metal grades, additional NDE beyond the code minimum, or stricter preheat requirements for cold-climate installations. The project-specific welding specification always takes precedence over the code baseline when it is more restrictive.
For transmission towers designed by PE-stamped drawings under AISC specifications, the AISC Chapter N quality control provisions also apply. When AISC certification is required for the fabricator, the welding quality control plan must conform to AISC Chapter N and AWS D1.1 together. See AISC 360 structural weld QC and AWS D1.1 for how these requirements interact.
Rule library based on AWS D1.1:2025; verify against your governing edition.
Common Base Metals in Lattice Tower Fabrication
A36: The workhorse of light lattice-angle towers. Group I prequalified base metal under AWS D1.1:2025 Table 5.6. Low-carbon equivalent — preheat generally not required for moderate thickness at ambient temperature.
A572 Grade 50: The dominant structural steel for medium and heavy lattice towers. Group II prequalified base metal per Table 5.6. The higher strength allows lighter sections than A36 for the same design load, reducing tower weight.
A588 and A709 Grade 50W: Weathering steel grades used in corrosion-resistant towers that are left unpainted. Both are Group II prequalified base metals. When welding weathering steel, the filler metal must also provide weathering-steel matching chemistry — ER70S-G or E8018-W type electrodes are typically required; standard ER70S-6 or E7018 provides adequate strength but not the weathering chemistry match.
A572 Grade 65: Higher-strength steel used in long-span or heavily loaded tower members. Grade 65 is not a prequalified base metal under Table 5.6 and requires a tested WPS supported by a PQR. See A572 Grade 65 structural steel WPS for the qualification path.
A913 Grade 65 or 70: Quenched and self-tempered high-performance steel used in large monopole shafts and heavy base plates. Requires a tested WPS and careful control of heat input to avoid HAZ degradation. Maximum interpass temperature is critical for A913.
Joint Types and Prequalified Details
Lattice tower fabrication involves a mix of fillet welds, partial joint penetration (PJP) groove welds, and occasional complete joint penetration (CJP) groove welds:
Gusset plate-to-chord angle connections. These are the most numerous joints in any lattice tower — fillet welds on both sides of the gusset plate connecting bracing angles and chord angles at panel points. Single-sided fillet welds are sometimes used on the accessible side only; the WPS must address single-pass vs. multi-pass and the accessible weld side.
Base plate-to-leg connections. The leg angle or leg tube frames into a base plate assembly. The connection is typically a CJP groove weld with backing, or a large fillet weld, depending on the design. CJP base plate connections require full qualification — prequalified groove details per Clause 5, Figure 5.1 if the geometry matches, or a tested WPS with a PQR if not.
Splice plate connections. Tower sections are often field-spliced using bolted splice plates with shop-welded attachment tabs. The tab welds in the shop are fillet welds and fall under a prequalified fillet WPS.
Pole shaft seam welds. Steel monopoles are fabricated from plate rolled into a conical or tapered cylinder. The longitudinal seam weld is a CJP groove weld, typically made by SAW in the shop. The WPS must address SAW essential variables under Table 6.6 and the prequalified SAW requirements in AWS D1.1.
Flange ring welds. Monopoles and sectional poles use bolted flange connections with continuous fillet welds or CJP groove welds between the flange ring and the pole shaft. These are high-fatigue details and may require additional NDE.
Preheat for Tower Base Metals
For A36 and A572 Grade 50 in member thicknesses common to lattice tower angles (up to about 1 in), preheat is typically not required at ambient temperature when using low-hydrogen filler metals. At thicknesses above about 3/4 in for A572 Grade 50, or when the carbon equivalent of the specific heat is elevated, minimum preheat applies per the applicable AWS D1.1:2025 table.
Cold-climate tower installations require particular attention: ambient temperature below 32°F [0°C] mandates minimum 70°F [20°C] preheat on all structural steel welds regardless of thickness. Wind and moisture at elevated installation sites can accelerate cooling rates — temporary wind shields and preheat monitoring are practical requirements that the CWI and field foreman must coordinate. See cold weather welding requirements under AWS D1.1 for preheat maintenance protocols in cold conditions.
For weathering steel (A588, A709 50W), preheat requirements follow the same logic as for A572 — based on thickness and carbon equivalent — with the added requirement that the filler metal chemistry must match the weathering-steel base metal if the weld is to provide the same corrosion resistance as the surrounding parent metal.